Alarm / control unit Floswitch
Product features
- Alarm and control unit for max. 10 digital inputs e.g. contact pressure gauge or pressure switch and 4 analogue inputs (e.g. pressure transmitters or weighting scales)
- The unit may be used for 1 switch-over-system and 2 individually programmable pneumatic valves, 2 switch-over systems or 4 individually programmable pneumatic valves
- Monitoring and display of the gas contents by pressure or by weight
- 1 cummulative potential free output for external monitoring (NO or NC)
- Solenoid valves can be manually operated by user
- 4 x 20 digits LCD-display with backlight
- Visual and acoustic alarm signals according to EN 737-3 and EN 475 (medical applications)
- Acoustic signals can be silenced
- Compatible with inductive sensors type DIN 19234 NAMUR 1-specification
- Compatible with inductive sensors type DIN 19234 NAMUR 1-specification
- Digital inputs to be configured for NO or NC contacts
- All operation parameters and signal configuration programmable by push-buttons placed on front panel
- Plastic housing IP 65 for wall mounting
- Password protection for superior level access
Technical data | ||
---|---|---|
Housing Protection class: Dimensions (WxHxD): |
IP 65 310 x 380 x 140 mm |
|
Compatibility inputs |
- mechanical switches - electr. switches PNP/NPN (DC only) - inductive switches type NAMUR |
|
Digital inputs Power supply voltage: Max. power: |
15 V DC 15 mA (per channel) |
|
Analogue inputs Max. voltage (open circuit): Short circuit current: |
24 V DC 25 mA |
|
Output / pneumatic valves Max. pressure: Compatibility: |
10 bar inert gases |
|
LCD-display |
4x20 digits w backlight | |
Power supply voltage Max. power consumption |
220 V / 50-60 Hz 100 mA |
|
Internal signals |
- LEDs 5 mm - piezo-buzzer |
|
NAMUR-Specification Voltage: Power input inactive: Power input activated: |
5 V DC - 25 V DC IL < 1 mA 3 mA < IL < 15 mA |
Скачать инструкцию в формате PDF